Viking i-8 Manuals & Support
Identify your model
The i-8 chassis is set in concrete below the gate hinge. The control box is above ground. Second generation units (2019 manual) use the VFlex board. First generation units (2009) use an older board and manual.
Key specs
| Type | In-ground swing operator with separate control box |
|---|---|
| Max gate | 650 lb / 12 ft |
| UL 325 usage class | Class I, II, III and IV |
| Operating voltage | 24 VDC |
| Main power | 115 VAC or 240 VAC single phase, 1.5 A / 1.0 A per operator |
| Alternative power | 24 VAC/VDC (60 VA) or solar |
| Limits | Mechanical |
| Operating temperature | -20 to 160 °F |
Manuals and documents
Installation Manual
-
i-8 Installation Manual, 2nd Generation
View PDF: i-8 Installation Manual, 2nd Generation (opens in a new tab) -
i-8 Manual, 1st Generation
View PDF: i-8 Manual, 1st Generation (opens in a new tab)
Troubleshooting
Common questions
A swing gate needs at least one monitored 10K sensor on the UL or Re-Open input. If there is an entrapment zone in the open direction, a sensor must be on UL. Wire them, then run the UL LEARN process from the Diagnose button.
Yes. Run a flexible drain pipe from the chassis to an area drain with enough slope that water does not collect around the motor.
No. Level the chassis both ways and align the pivot with the upper hinge before the concrete cures. Check it again before it sets.
The alarm sounds after a second obstruction in a row. Remove the obstruction and press the Alarm Reset button on the operator.