EMX ULT-MVP-2 Manuals & Support
Identify your model
The ULT-MVP-2U uses US wiring and the ULT-MVP-2E uses European wiring on the 11-pin plug. Check the model on the side label before you wire a socket.
Key specs
| Channels | 2 loops, 2 relay outputs |
|---|---|
| Power | 12 VDC to 240 VAC |
| Connector | 11-pin plug (LD-11 socket or HAR-11 harness) |
| Relay rating | 2 A at 30 VDC, 0.5 A at 125 VAC |
| Sensitivity | 10 levels, 0 to 9, with ULTRAMETER display |
| Loop frequency | 4 settings |
| Loop inductance | 20 to 2,000 µH |
| Modes | Presence, pulse, AB logic direction, Detect-On-Stop, automatic sensitivity boost |
| Size | 73 x 38 x 78 mm |
Manuals and documents
Installation Manual
-
ULT-MVP-2 Instruction Manual
View PDF: ULT-MVP-2 Instruction Manual (opens in a new tab) -
Loop Wire Installation
View PDF: Loop Wire Installation (opens in a new tab) -
Lite Preformed Loop Instructions
View PDF: Lite Preformed Loop Instructions (opens in a new tab)
Spec Sheet
-
ULT-MVP-2 Spec Sheet
View PDF: ULT-MVP-2 Spec Sheet (opens in a new tab)
Other documents
-
EMX Loop Size Chart
View PDF: EMX Loop Size Chart (opens in a new tab) -
TSTL Test Loop Instructions
View PDF: TSTL Test Loop Instructions (opens in a new tab)
Troubleshooting
Common questions
Yes. It plugs into an 11-pin LD-11 DIN rail socket or a HAR-11 harness. Neither is included.
The output turns on only after a vehicle stops on the loop for about 1 to 2 seconds. It helps ignore cross traffic in tight spaces.
Yes. With two loops in the lane, AB logic mode gives a direction output based on which loop the vehicle crosses first.
Use direct-burial loop wire such as 16 AWG XLPE, not THHN. Twist the lead-in about 6 turns per foot from the loop to the detector, and seal saw cuts with loop sealant.