EDI LMA-1800 and LMA-1800-LP Loop Detectors Manuals & Support

EDI LMA-1800 / LMA-1800-LP

The EDI LMA-1800 is a single channel DEFLECTOMETER loop detector that plugs into a gate operator 10-pin Molex detector port. It has two programmable solid-state outputs and runs on 10 to 30 VDC or 14 to 26 VAC.

The DEFLECTOMETER display shows the detection level so sensitivity can be set to catch every vehicle. The LMA-1800-LP is the low power version for solar and battery operators.

Buy the LMA-1800 / LMA-1800-LP (4 options)

Identify your model

Both are 2.30 x 2.75 x 0.80 in with a rear 10-pin Molex connector (09-48-1104). LP is printed on the low power model. The discontinued LMA-1500 and LMA-1500-LP are replaced by these models.

Key specs

Channels 1 loop, 2 solid-state outputs
Outputs Open collector, 100 mA at 30 VDC
Power 10 to 30 VDC or 14 to 26 VAC
Connector 10-pin Molex
Sensitivity 10 levels
Loop frequencies 4
Loop inductance 20 to 2,500 µH
Operating temperature -30 to 165 °F

Manuals and documents

Installation Manual

Spec Sheet

Other documents

Troubleshooting

Gate does not open or reopen

  • Check the detect LED when a vehicle is on the loop.
  • Raise the sensitivity one step at a time.

Detector stays in detect

  • Check the loop and lead-in for a break or short to ground.
  • Reset the detector so it retunes.

Random detects

  • Set nearby detectors to different frequencies.
  • Check that the lead-in is twisted and the saw cut is sealed.

Common questions

Operators with a 10-pin Molex detector port, such as many LiftMaster/Elite, All-O-Matic, Linear, Viking and Apollo models. Check the EDI cut sheet list.

Use the LMA-1800-LP on solar and battery operators.

Use direct-burial loop wire such as 16 AWG XLPE, not THHN. Twist the lead-in about 6 turns per foot and seal saw cuts with loop sealant.