Linear VS-GSWG Variable Speed Swing Gate Operator Manuals & Support

Linear VS-GSWG

The Linear VS-GSWG is an industrial variable speed swing gate operator with a linear drive arm. It handles gates up to 36 ft and 1,500 lb with the 2 HP model and is rated for continuous duty.

A variable frequency drive gives soft start and stop. It runs on single phase or three phase power and uses the APeX controller with a built-in MegaCode receiver.

Buy the VS-GSWG (14 options)

Identify your model

The model code gives HP and power: VS-GSWG-2xx is 1/2 HP, -1xx is 1 HP and -7xx is 2 HP. It mounts on posts with a galvannealed steel cabinet. The non-variable model is the SWG.

Key specs

Max gate 1/2 HP: 1,000 lb / 28 ft; 1 HP: 1,200 lb / 32 ft; 2 HP: 1,500 lb / 36 ft
Motor 1/2, 1 or 2 HP industrial three-phase, 56 frame
Power 115 or 230 VAC single phase; 208, 230 or 460 VAC three phase
Open time 18 to 22 seconds
Speed control Variable frequency drive, soft start and stop
Drive 60:1 C-face gear reducer, linear drive arm, adjustable torque limiter
Mount Post mount; pad mount optional
Approvals UL 325 and UL 991

Manuals and documents

Installation Manual

Wiring Diagram

Spec Sheet

Other documents

Troubleshooting

The APeX controller shows status on its 2-digit display and LEDs. Press STOP to clear most errors once the cause is fixed.

Error codes

  • En 00: two safety reversals in a row. Clear the obstruction and press STOP.
  • En 01 or En 02: maximum run timer ran out while opening or closing. Check for a broken chain or belt, a slipping pulley or a timer set too low.
  • En 03: dual gate COMM LINK failure. Check the 3-wire shielded cable between operators.
  • En 04: battery dropped below 21.6 VDC after AC power loss. Restore AC power and let the batteries charge.
  • En 07: low AC voltage at the controller. Restore normal supply voltage.
  • En 10: EEPROM problem. Try a reset.
  • En 11: DC motor check failed. Reprogram the motor type.

Operator fails to start

  • The motor thermal overload may have tripped after many cycles. Let it cool and it resets.
  • Check power at the breaker panel.

Gate stops part way with no obstruction

  • Current sensing set too low. Make sure the gate moves freely, then raise the setting.
  • An accessory on the obstruction input triggered. Disconnect devices one at a time to find it.

Motor runs but gate does not move

  • Check the torque limiter for slipping and tighten it if needed.
  • Check for a broken chain or worn belts and loose set screws or keys.

Common questions

Yes. The APeX controller has an integral MegaCode receiver that learns up to 40 Linear MegaCode transmitters.

The operator saw two safety reversals in a row and locked out. Clear the obstruction, then press STOP to reset.

Use 1/2 HP for gates up to 28 ft and 1,000 lb, 1 HP up to 32 ft and 1,200 lb, and 2 HP up to 36 ft and 1,500 lb.